54 NFS2-3030/E Installation Manual — P/N 52544:N1 07/18/2014
Applications Connecting a Releasing Device to FCM-1 Control Modules (Retrofit applications only)
a) End-of-Line devices (P/N REL-47K) are not required; however, the releasing device circuit
is not supervised against shorts.
b) Limited energy cable cannot be used for wiring of a releasing device circuit.
c) Maintain a 0.25 inch (6.35 mm) spacing between the releasing circuit device wiring and any
power-limited circuit wiring.
d) In non-power-limited applications, program the releasing circuit for Type Code
RELEASE CKT
.
NOTE: As per UL 864 9
th
edition, a supervisory signal must be indicated at the panel whenever
a releasing circuit is physically disconnected. Use a monitor module to monitor dry contacts off the
switch. See figure 4.12. Refer to the SLC Manual for detailed wiring information.
Figure 4.12 Typical Connection of a Mechanical Disconnect Switch
gasdisconnectmod.wmf
Mechanical Disconnect Switch listed for the application
Note: Disconnect switch must provide separate dry
contacts to indicate supervisory.
Monitor Module

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Notifier NFS2-3030/E and is the answer not in the manual?

Notifier NFS2-3030/E Specifications

General IconGeneral
BrandNotifier
ModelNFS2-3030/E
CategoryControl Panel
LanguageEnglish

Related product manuals