EasyManuals Logo

NTI ENVIROMUX Series Manual

NTI ENVIROMUX Series
59 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #30 background imageLoading...
Page #30 background image
NTI ENTERPRISE ENVIRONMENT MONITORING SYSTEM
29
From the Alert Settings menu, the user can enable/disable alert messages to be sent when the IP Device is not responding and
configure when and how alert messages are sent.
Figure 28- Text Menu-IP Device Alert Settings
Alert Settings Description
Disable alerts Change to “Yes” to prevent alerts from being sent when this IP Device’s status changes
Notify Again Time Enter the amount of time in seconds, minutes, or hours (1-999) before an alert message will be
repeated
Notify on Return to Normal The user can also be notified when the IP Device’s state has returned to the normal by
changing to “Yes” for "Notify on return to normal" for a sensor.
Auto Acknowledge Change to “Yes” to have alert notifications in the summary page return to normal state
automatically when sensor readings return to normal.
Enable Email Alerts Change to “Yes” to have alert notifications sent via Email
Enable Syslog Alerts Change to “Yes” to have alert notifications sent via Syslog messages
Enable SNMP traps Change to “Yes” to have alert notifications sent via SNMP traps (v2c)
Email Subject Enter the subject to be viewed when an email alert message is received
Enable SMS Alerts Change to “Yes” to have alert notifications sent via SMS (requires GSM modem)
Siren Change to “Yes” to activate the siren circuit during an alert condition
Beacon Change to “Yes” to activate the beacon circuit during an alert condition
Press <Tab> to highlight Save and press <Enter> to save before pressing <Esc> to exit.

Table of Contents

Other manuals for NTI ENVIROMUX Series

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the NTI ENVIROMUX Series and is the answer not in the manual?

NTI ENVIROMUX Series Specifications

General IconGeneral
Product TypeEnvironmental Monitoring System
Temperature Range-40°C to 85°C
Power Supply12V DC or 24V AC
Network InterfaceEthernet 10/100 Mbps
Alarm NotificationsEmail, SNMP
Sensor Types SupportedTemperature, Humidity, Water, Airflow
Power12V DC or 24V AC
Operating Temperature-40°C to 85°C
MountingWall or Rack Mount
Communication InterfacesEthernet
Data LoggingYes
ComplianceCE, RoHS

Related product manuals