EasyManua.ls Logo

Oldham iTrans 2

Oldham iTrans 2
106 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
84
44-49
Latin-1 ASCII
Manufacture Date
Command 135 Read Calibration Data Response Length: 18 Bytes
Byte Number
Parsing
Parameter
0-3
Float IEEE 754
Span Reserve Value Channel 1
4
Unsigned-8
Last Cal Day Channel 1
5
Unsigned-8
Last Cal Month Channel 1
6
Unsigned-8
Last Cal Year Channel 1
7-8
Unsigned-16
Next Cal Due In Days Channel 1
9-12
Float IEEE 754
Span Reserve Value Channel 2
13
Unsigned-8
Last Cal Day Channel 2
14
Unsigned-8
Last Cal Month Channel 2
15
Unsigned-8
Last Cal Year Channel 2
16-17
Unsigned-16
Next Cal Due In Days Channel 2
Table A - 3 Read Commands
Write Commands
All write commands are dispatched with specific number of data bytes
which are written to specified parameters after parsing process. In case of a
single sensor the parameters of disconnected sensor are also
included in the request data although those can be set at 0. The response of
a write command is the same as the request. The details are provided in the
Table A - 4.
Command 140 Write Real Time Clock Response/Request Length: 18 Bytes
Byte Number
Parsing
Parameter
0
Unsigned-8
RTC Minute Channel 1
1
Unsigned-8
RTC Hour Channel 1
2
Unsigned-8
RTC Day Channel 1
3
Unsigned-8
RTC Month Channel 1
4
Unsigned-8
RTC Year Channel 1
5-8
Unsigned-32
Total Operation Time (In Minutes) Channel 1
9
Unsigned-8
RTC Minute Channel 2
10
Unsigned-8
RTC Hour Channel 2
11
Unsigned-8
RTC Day Channel 2
12
Unsigned-8
RTC Month Channel 2

Table of Contents

Related product manuals