4-Analog Output Module
 
Function 
 
This digital module delivers 1 to 4 
discrete opto-isolated analog outputs 
deactivated. Several detectors can be 
assigned to one output allowing the 
management of the lowest, highest 
and averaged value. When non 
configured, the analog output is set to 
0mA. The module also features two 
logic inputs. 
 
 
 
Figure 20: 4 Analog Output Module 
Introduction 
 
Power supply and RS485 network
 
DIP switches for module configuration
 
Push-button. Pressing this button 
forces all outputs to 20mA
 
(E1 to E4) discrete opto-isolated    
4-20mA analog outputs
 
(F1 to F4) current output settings. 
Press D and set to 20mA
 
Figure 21: 4 Analog Output Module 
A – Logic input connectors
 
Each of these two terminals (Figure 21) may be connected to a voltage-free 
contact in accordance with Figure 31 
C – Module configuration DIP switches
 
These switches are set according to the following table:
 
Slave number 
Numéro esclave
 
See details in the paragraph Module Address on page 18
 
Frame filling 
Remplissage de trame
 
Factory settings. Do not modify 
Factory settings. Do not modify 
E.O.L. Resistor 
Résistance F.D.L.
 
See details in paragraph End of line Resistor, on page 19
 
Table 9: Analog Output Module Configuration DIP switches 
Connection
 
Refer to Chapter 6, on page 27
 
Configuration
 
Configured via the COM 32 application