45
Display Appendix (continued) Section Eight
HOW TO REVERSE THE CURRENT OUTPUT
The factory setting for LVU700 series has 4mA set at the bottom of the tank and 20mA at the top. If the
application requires this output to be reversed (20mA at bottom and 4mA at top), then use the REV MA setting
to reverse the current output.
With REV MA set to NORM (factory default), 4mA will be at the bottom and 20 mA at the top of the tank.
With REV MA set to REV, 20mA will be at the bottom and 4mA at the top of the tank.
1. In TOP-LEVEL MENU mode, select
OUTPUT.
2. Select REV MA.
3. Select 4 BOTT or 4 TOP.
a. Press and hold OK on the selected
setting for 3 seconds then release.
b. To cancel REV MA, Select EXIT.
4. Select EXIT to return to TOP-LEVEL MENU.