Introduction (continued) Step One
SPECIFICATIONS
Electrical:
Supply Voltage: 14-28 Vdc
Signal: 4 to 20 mA current loop; 22 mA
max.
Mechanical:
Display Module: Removable via short cable and
plug
LCD: 6 characters, 10 mm (0.394”)
height
Buttons: Three, UP / OK / DN
Pin Connection: Display can be removed such
that the open connection allows
the sensor to be LVCN414-SW
software capable.
Enclosure: Polypropylene head with skirt to
support transducer w/ conduit
Conduit Connection: Single, 1/2 inch NPT
Transducer: Black, PVDF with FKM gasket
Process Mount: LVU706: 2" NPT or 2” G
LVU712: 3” NPT or 3” G
Gasket FKM (G thread only)
Electrical Connections:
Power & Return: 2-pin removable terminal block
Display Connect.: 4-pin removable terminal pins
Non-Display
version.: Block optional with FOB
* Earth ground on package
external
Environmental:
Process Temp.: -40 to 80 °C (-40 to 176 °F)
Temp. comp.: Automatic
Ambient Temp.: -35 to 60 °C (-31 to 140 °F)
Pressure: 30 psi, derated @ 1.667 psi per
degree C above 25 °C
Enclosure: NEMA 6P, IP68
Functional:
Range: LVU706: 6.0m (19.69 feet)
LVU712: 12.0m (39.4 feet)
Dead band: LVU706: 20cm (8 inches)
LVU712: 45.7cm (18 inches)
Accuracy: 0.2% of Range in air at 20 °C
Resolution: LVU706: 2mm (0.079 inches)
LVU712: 5mm (0..196 inches)
Beam width: LVU706: 7.6cm (3 inches)
LVU712: 15.2cm (6 inches)
Menu: Self-scrolling