A-15
  Appendices
CJ-series PROFIBUS Master Unit Operation Manual for NJ-series CPU Unit (W509)
A-5 CX-ConfiguratorFDT Warning and Error Messages 
App
 
The table below lists the Error messages which can be displayed by the PROFIBUS Master Unit DTM
in case there are configuration errors. Usually, these are detected either when entering, or up on down-
load. The table suggests corrections to the problems in the right most column.
07 [IO area] must be empty. 
Move all modules into other 
area
• [IO area] = output area1/ 
output area2/ input area1/ 
input area2
“Not used” item in the start address combo box in 
output/input allocation tabs can only be selected if 
there are no I/O module mapped in that area.
• OKClose message box. Move modules to other 
I/O area first.
When selecting the “Not 
Used” item from the 
memory area box.
08 Slave_User_data part of the 
PROFIBUS slave parameter 
set will be ignored. See slave 
[no]-[name]
[no] = slave address
[name] = slave DTM name
Slave_User_data part of the slave parameter set 
will not be used. The additional user parameters 
in the slave parameter set are not supported by 
the PROFIBUS Master Unit.
• OK: Close message box
When adding a slave 
DTM to the network, 
which defines additional 
user parameters.
09 Auto addressing will reallo-
cate slave I/O mapping. 
Would you like to proceed?
When selecting the Auto-Addressing check box in 
the Master Setup tab, all slave I/O data mappings 
will be compressed in each of the I/O mappings. 
The slave I/O mapping will be changed.
• Yes: Update slave I/O module mapping and 
check checkbox.
• No: Do not update slave I/O module mapping 
and uncheck checkbox.
When checking the Auto-
Addressing checkbox on 
the Master Setup tab.
10 Settings cannot be uploaded, 
unit must be restarted. Would 
you like to continue? 
The settings uploaded were not used by stack
• Yes: Restart the unit and upload the settings.
• No: Do nothing.
When attempting to 
upload settings.
11 Upload is not supported. Upload is not supported
OK: Close message box.
When attempting to 
upload settings.
12 After locking address it can-
not be changed any more. 
Would you like to proceed?
When sending Set Device Station Address com-
mand with 'Lock' check box is checked, the 
address will be stored permanently in the Slave 
device and can not be changed anymore. 
• Yes: Lock option is checked.
• No: Lock option is unchecked.
When ‘Lock’ check box in 
the Set Device Station 
Address GUI is checked.
13 PROFIBUS DP-V1 alarms 
are not supported by the 
Master Unit and will be dis-
abled.
Alarm settings set by the Slave DTM are not sup-
ported and will be reset.
• OK: Close message box.
Downloading settings and 
one of the alarm bits are 
set in Slave Parameter 
Set.
14 Publisher functionality is not 
supported by the Master Unit 
and will be disabled.
Publisher functionality set by the Slave DTM is not 
supported and will be reset.
• OK: Close message box.
Downloading settings and 
the Publisher bit is set in 
Slave Parameter Set.
15 Isochronous mode is not sup-
ported by the Master Unit and 
will be disabled.
Isochronous mode set by the Slave DTM is not 
supported and will be reset.
• OK: Close message box.
Downloading settings and 
the Isochronous mode bit 
is set in Slave Parameter 
Set.
16 Acyclic Connection / Abort 
Status Area and Acyclic Slave 
Timeout settings are not sup-
ported by the Master Unit and 
will be disabled.
The connected Master Unit has version V2.00. 
The new features for version V3.00 (and up) are 
not supported by the Master Unit.
Downloading settings to 
Master Unit V2.00 with 
Master DTM V3.00 (or 
higher).
Configuration Error Messages
Number Message Description When occurring