A-17
Appendices
CJ-series PROFIBUS Master Unit Operation Manual for NJ-series CPU Unit (W509)
A-5 CX-ConfiguratorFDT Warning and Error Messages
App
16 Master Unit indicated failure
of Set Device Station
Address.
When sending Set Device Station
Address command, one of the follow-
ing problems occurred:
The slave has deactivated this ser-
vice.
The slave has not responded to the
request.
The slave does not have sufficient
memory space for the request data.
Check target Slave device on the
PROFIBUS network.
Check specified Slave address.
Check Slave timeout parameter
17 'New address' and/or 'Ident
number (hex)' are/is empty.
No data is entered in the New
Address and Ident Number fields.
Fill-in both the 'New address' and the
'Ident number (hex)' fields.
18 Slave/Master DTM does not
accept the specified address.
The DTM has not accepted the new
address setting. Possible cause is
that the slave DTM data set has been
locked for parameter changes.
19 Master Unit version and DTM
version do not match. Please
select DTM that can be used
with the connected device
(refer to section 1-2-2 Specifi-
cations).
The selected DTM is not suitable to
configure the connected PROFIBUS
Master.
Please use the DTM as specified in
the error message.