9 Troubleshooting and Maintenance
9-38
CJ-series DeviceNet Units Operation Manual for NJ-series CPU Unit(W497)
34C20000 hex Slave I/O
Refresh Error
The I/O memory in
the destination
CPU Unit for I/O
refreshing could not
be found when
refreshing the slave
function data in the
CPU Unit.
I/O words are allocated in an
EM bank that does not exist.
S
page 9-48
34C30000 hex Slave User
Allocation
Area Setting
Failed
An error occurred in
the following opera-
tion for user alloca-
tion of the slave.
The slave function is not dis-
abled.
There is a mistake in the user
allocations to a slave.
CPU Unit is not in PROGRAM
mode.
More than one software switch
changed to TRUE at the same
time. Or, another software
switch changed to TRUE before
processing was completed for a
previous software switch.
S
page 9-48
64AC0000 hex Send Time-
out Error
A send timeout
occurred.
There is no slave or other
device on the network.
The same baud rate is not set
for all nodes.
Communications cable lengths
(trunk line and branch lines) are
unsuitable.
A communications cable is dis-
connected or loose.
The terminating resistance is
somewhere other than the ends
of the trunk line.
Noise
There is an error in the CAN
controller.
S
page 9-49
74600000 hex Master Func-
tion
Enable/Dis-
able Failed
An operating error
occurred when
enabling or dis-
abling the master
function.
An attempt was made to enable
the master function when it was
already enabled.
An attempt was made to dis-
able the master function when it
was already disabled.
CPU Unit is not in PROGRAM
mode.
More than one software switch
changed to TRUE at the same
time. Or, another software
switch changed to TRUE before
processing was completed for a
previous software switch.
S
page 9-50
74610000 hex Master Fixed
Allocation
Area Setting
Failed
An error occurred in
one of the following
operations for fixed
allocation of the
master.
The master function is not
enabled.
The scan list is not disabled.
CPU Unit is not in PROGRAM
mode.
More than one software switch
changed to TRUE at the same
time. Or, another software
switch changed to TRUE before
processing was completed for a
previous software switch.
S
page 9-51
Event code Event name Meaning Assumed cause
Level
Reference
Maj Prt Min Obs Info