92
Relay Output Units Section 4-5
Dimensions
Note The vertical center of the Unit is 4.9 mm lower than the center of the DIN
track. The Unit therefore extends downward 41.4 mm (including the mounting
hook) from the DIN track center.
4-5-2 GT1-ROS16 Relay Output Unit with Miniature Relay
Output Specifications
Reference Data
For details about the Relay characteristics, refer to G6D-1A in the PCB Relays
Catalog (X033). The following table shows how the number of outputs that
can be ON simultaneously varies with the ambient temperature.
(Unit: mm)
Approx. 82
Approx. 68
60
160
2
4
65
37.4
27.6
12.
6
35
Item Specifications
Number of outputs 16 points
Relay Miniature Relay (G6D-1A 24 VDC)
Rated load (resistive load) 2 A at 250 VAC/2 A at 30 VDC
Rated thermal current 2 A
Maximum switching voltage 250 VAC/30 VDC
Maximum switching current 2 A
Minimum permissible load 10 mA at 5 VDC (P level reference value)
Insulation resistance 1,000 MΩ
Ambient temperature (°C)
Maximum number of outputs