EasyManua.ls Logo

Omron DEVICENET#05-2003 - Exchanging Data

Omron DEVICENET#05-2003
233 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
10
Functions Section 1-2
Indicators
For details, refer to page 199, Troubleshooting via Indicators.
Checking the I/O Unit Interface Status
The first two words of the CPU Unit allocation input area are always allocated
to the status of the I/O Unit interface via the DeviceNet.
1-2-2 Exchanging Data
Initialization When the Communications Unit is started, it automatically recognizes the
configuration of the I/O Units and registers this status as the normal configu-
ration (in RAM memory). At the same time, addresses 0 to 7 are allocated to
the I/O Units in ascending order from the I/O Unit closest to the Communica-
tions Unit. These processes are performed each time the power is turned ON.
Unit Normal Error
Communications
Unit
TS Indicator:
Lit green
TS indicator
I/O Unit interface error: Lit red
Special I/O Unit error: Flashing green
Maximum power supply
overload to I/O Units: Not lit
I/O Units TS indicator:
Lit green
U.ERR indica-
tor: Not lit
PWR indicator:
Lit green
TS indicator
I/O Unit interface error: Lit red
U.ERR indicator
Special I/O Unit error: Lit red
PWR indicator
No internal power supply: Not lit
DeviceNet
Network
Communica-
tions Unit
I/O Unit I/O Unit
TS indicator
Output
area
Input
area
Status, two words
I/O Unit connection information
Error slaves Registered slaves
For details, see page 15.
DeviceNet Master Unit
DeviceNet Network
Communica-
tions Unit
I/O Unit I/O Unit
0 wd
+1 wd

Table of Contents

Related product manuals