124
Analog Output Units Section 5-2
5-2 Analog Output Units
5-2-1 GT1-DA04
General Specifications
Characteristics
Item Specification
I/O connections Terminal block (M3)
Number of outputs 4 outputs (allocated four words in the Master Unit)
Internal
power sup-
ply
Voltage range
20.4 to 26.4 VDC (24 VDC
+10%
/
–15%
)
Current consump-
tion in Unit (inrush
current)
150 mA max.
(inrush current 20 A max., pulse width 1ms max.)
Current consumption
(I/O Unit interface)
50 mA max.
Noise immunity ±2000 V
(IEC61000-4-4 via fast transient noise simulator)
Vibration resistance
10 to 150 Hz, 1.0-mm double amplitude or 70 m/s
2
Shock resistance
200 m/s
2
Ambient temperature –10°C to 55°C
Ambient humidity 25% to 85% (with no condensation)
Operating atmosphere No corrosive gases
Storage temperature –25°C to 65°C
Safety standards UL508, CSA22.2
EMC directives EN50081-2, EN50082-2
Mounting DIN 35-mm track
Weight Approx. 230 g
Item Specification
Voltage outputs Current outputs
Output signal range 0 to 5 V, 1 to 5 V, 0 to 10 V, or
–10 to 10 V
4 to 20 mA
Allowable external out-
put load resistance
5 K min. 600 min.
External output imped-
ance
0.5 max. ---
Resolution 1/6000 (full scale)
Accuracy 25°C ±0.4% FS
–10°C to
55°C
±0.8% FS
Conversion time 4 ms/4 points
Converted output data
(Binary)
Binary
–10- to 10-V range: F448 to 0 to 0BB8 full scale
Other signal ranges: 0000 to 1770 full scale
Dielectric strength 500 VAC; detected current 1 mA (between communications
section and analog output, and between internal power
supply and analog output)
Isolation method Photocoupler insulation (between communications part and
analog output)
(no insulation between analog outputs)

Table of Contents