120
Analog Input Units Section 5-1
6. Click Adjustment.
The Unit Adjustment Window will be displayed.
7. Click the Down Arrow and select the input words and the input range to be
adjusted.
8. Apply the input voltage or input current corresponding to 0% to the input
terminal on the Analog Input Unit.
9. Click Fix Offset Value when the appropriate input voltage or input current
has been applied according to step 8.
The offset will be set so that the input voltage or input current are converted
to a value of 0%, and the value of the offset will be stored in the EEPROM
in the Analog Input Unit. Reset the Unit to enable the new setting.
10. Apply the input voltage or input current corresponding to 100% to the input
terminal on the Analog Input Unit.