127
Analog Output Units Section 5-2
Terminal Arrangement
Wiring
Output Ranges and
Converted Data
The Analog Output Unit converts the digital output data to analog values. The
analog values depend on the output signal ranges, as shown in the following
diagrams.
1 to 5 V
The hexadecimal values 0000 to 1770 (0 to 6000) correspond to an analog
voltage range of 1 to 5 V. The entire output range is 0.8 to 5.2 V.
Internal power supply
Internal power
supply
Voltage output
External
output
Current output
External
output
Voltage
5.2 V
5 V
1 V
0.8 V
0 V
FED4
(−300)
1770
(6000)
189C
(6300)
8000
0000 (0)
7FFF
Converted data
Hexadecimal
(Decimal)