129
Analog Output Units Section 5-2
4 to 20 mA
The hexadecimal values 0000 to 1770 (0 to 6000) correspond to an analog
current range of 4 to 20 mA. The entire output range is 3.2 to 20.8 mA.
Output Status after
Communications Error
The Configurator or pins 8 and 9 of the DIP switch can be used to determine
the status of the outputs after a communications error occurs in DeviceNet or
I/O Unit interface communications. The following settings are possible:
Hold (maintain previous output status)
Clear to minimum (clear to the lower limit of the output signal range)
Clear to maximum (clear to the upper limit of the output signal range)
Clear to 0 V (for –10 to 10 V only)
When the clear to minimum, clear to maximum, or clear to 0 V setting is used,
the output data will be as shown in the following table.
Converted Data Output the converted data to the Master as shown in the following diagram.
When a negative voltage is to be output, specify the conversion data as the
two’s complement. To obtain a two’s complement from an absolute value, the
NEG instruction is useful.
Conversion Time The conversion data is refreshed every 4 ms for all 4 points.
Current
20.8
mA
20 mA
4 mA
3.2 mA
0 mA
FED4
(
300)
1770
(6000)
189C
(6300)
8000
0000 (0)
7FFF
Converted data
Hexadecimal
(Decimal)
Output signal range Clear to minimum Clear to maximum Clear to 0 V
0 to 5 V –0.25 V 5.25 V –0.25 V
1 to 5 V 0.8 V 5.2 V 0.8 V
0 to 10 V –0.5 V 10.5 V –0.5 V
–10 to 10 V –11 V 11 V 0 V
4 to 20 mA 3.2 mA 20.8 mA 3.2 mA
Bit
First word
First word + 1
First word + 2
First word + 3
Output 0 data
Output 1 data
Output 2 data
Output 3 data