Analog Output Units Section 5-2
DIP Switch Settings The following diagram shows the functions of the DIP switch.
The following table summarizes the DIP switch settings. (All pins are factory-
set to OFF.)
Note 1. When setting the output range or output for communications errors using
a DeviceNet Configurator, use version 1.11 or later. (If pin 10 is ON, and a
setting is made using the Configurator, the output ranges will all be 0 to 5
V and the output for communications errors setting will be set to clear to
minimum.)
2. Make sure the I/O Unit power supplies (including the I/O Unit interface
power supply) are OFF when setting the DIP switch.
3. With an Analog Output Unit, outputs for communications errors is enabled
using the switch on the Analog Output Unit. It does not depend on the
Communications Unit “hold/clear communications error” setting.
Output Range Settings
As shown in the following table, the DIP switch output range settings are for
two outputs each.
Pin(s) Function Settings Meaning
1 through 6 Output range Output range settings (See below.)
7 Reserved for system use OFF Must be set to OFF.
8, 9 Output for communications
errors
(See below.)
89Output
OFF OFF Clear to minimum
(See below.)
OFF ON Clear to maximum
(See below.)
ON OFF Clear to 0 V
(for –10 to 10 V)
Clear to minimum
(other than the above)
ON ON Hold
10 Software setting enable/
disable
OFF Set the output range, and
output for communications
errors, with pins 1 to 9. (fac-
tory-set)
ON Output range setting (See
note.) and output setting for
communications errors can
be set using the Configura-
tor.
Operating specifications
Output for communications errors
Software setting enable/disable
Output
range
ON
Pin 1 Pin 2 Pin 3 Output range settings for outputs 0 and 1
Pin 4 Pin 5 Pin 6 Output range settings for outputs 2 and 3
OFF OFF OFF 0 to 5 V (factory-set)
ON OFF OFF 1 to 5 V
OFF ON OFF 0 to 10 V
ON ON OFF –10 to 10 V
Other than the above Cannot be set