134
Analog Output Units Section 5-2
Wiring Attach MOLEX connectors to the analog output connectors, and connect the
outputs as shown in the following diagram.
Applicable Connectors
Output Ranges and
Converted Data
The Analog Output Unit converts the digital output data to analog values. The
analog values depend on the output signal ranges, as shown in the following
diagrams.
1 to 5 V
The hexadecimal values 0000 to 1770 (0 to 6000) correspond to an analog
voltage range of 1 to 5 V. The entire output range is 0.8 to 5.2 V.
Manufac-
turer
Connector Model number Remarks
MOLEX Pressure-
welded
Housing 521-09-0390 For AWG#24
Crimp Housing 50-57-9403
Reeled contacts 16-02-0069 For AWG#24 to 30
16-02-0086 For AWG#22 to 24
Loose contacts 16-02-0096 For AWG#24 to 30
16-02-0102 For AWG#22 to 24
Crimping tool 570-36-5000 For AWG#22 to 26
11-01-0209 For AWG#24 to 30
External
device
Power
supply
24 VDC
+
−
Voltage
5.2 V
5 V
1 V
0.8 V
0 V
FED4
(−300)
1770
(6000)
189C
(6300)
8000
0000 (0)
7FFF
Converted data
Hexadecimal
(Decimal)