156
GT1-TS04T and GT1-TS04P Temperature Input Units Section 5-3
6. Double-click the line for the input range to be changed or, alternatively,
click Set Parameters once with the line selected.
The Parameter Setting Window will be displayed.
7. Select the desired input range and click OK.
The input range will be set and the window for step 6 will appear again.
8. To change other input ranges, repeat steps 6 and 7.
9. When all the required input ranges have been set, click OK in the Edit Unit
Parameters Window for the Temperature Input Unit. The Edit Device Pa-
rameters Window for the Communications Unit will appear again.
10. To make the settings for other I/O Units, repeat steps 5 to 9.