168
GT1-TS04T and GT1-TS04P Temperature Input Units Section 5-3
7. Click the Down Arrow to select the input words, the input type, and the in-
put range to be checked.
8. Click Check.
The Check Unit Window will be displayed.
9. Check the lower limit as follows:
•GT1-TS04T
Check that the cold contact compensator is operating at 0
°C, then apply a
voltage equivalent to the lower limit of the conversion range to the input ter-
minal (as selected in step 7) on the Temperature Input Unit from the stan-
dard voltage/current generator.
•GT1-TS04P
Apply a resistance equivalent to the lower limit of the conversion range to
the input terminal (as selected in step 7) on the Temperature Input Unit
from the 6-dial precision resistance box.
Check that the temperature data equivalent to the voltage or resistance input
is correctly displayed as the Current Value.
10. Repeat step 9 for the median value and the upper limit.
11. To continue checking other inputs, click Close to return to the Edit Unit
Window, and then repeat steps 7 to 10.
12. When you have completed all the checks, click Close.
A message asking if you want to reset will appear. Click Yes. The Commu-
nications Unit and all I/O Units connected to it will be reset, and the Unit
will return to normal operating mode from Calibration Mode. The Edit Unit
Parameters Window for the Temperature Input Unit.