GT1-TS04T and GT1-TS04P Temperature Input Units Section 5-3
4. Click Set on the right of the Temperature Input Unit to be cleared. Unit 1
to Unit 8 correspond to I/O Units #0 to #7.
The Edit Unit Parameters Window for the Temperature Input Unit will be
displayed.
5. Click Calibration.
The Calibrate Unit Window will be displayed. At this time, the Temperature
Input Unit will enter Calibration Mode. While in Calibration Mode, temper-
ature data sent to the Master will be 7FFF Hex. (7FFFFFFF Hex if in 2-dec-
imal-place Mode). Exit the Calibration Mode by resetting the MULTIPLE I/
O TERMINAL, or by turning the power OFF and ON again, to return to nor-
mal operating conditions.
6. Click Set Default.