EasyManua.ls Logo

Omron DEVICENET#05-2003 - Page 91

Omron DEVICENET#05-2003
233 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
80
Transistor Output Units Section 4-4
Connector Cables
When a Transistor Output Unit (connector) is to be connected to an OMRON I/
O Block or a Connector-Terminal Block Conversion Unit, use the cables (sold
separately) listed in the following table.
Note V terminals and G terminals are internally connected. When the I/O power is
being supplied, the power can be supplied to the output devices from the V
and G connectors. Current supplied in this way, however, must be less than
2 A. If, instead of using the V and G connectors, the power supply is wired to
the terminal block as shown in the following diagram, the current supplied
must be less than 2.5 A.
Dimensions
Note The vertical center of the Unit is 4.9 mm lower than the center of the DIN
track. The Unit therefore extends downward 41.4 mm (including the mounting
hook) from the DIN track center.
Manufacturer Model number Corresponding device
OMRON XW2Z-@@@A Connector-Terminal Block Conversion Unit
XW2B-20G4
XW2B-20G5
G79-@@@C I/O Block
G7TC-OC16-1
G70D-SOC16-1
G70D-FOM16-1
G70A-ZOC16-4
M7F
Output Unit
I/O Block (example)
Load
(Unit: mm)
Approx. 59

Table of Contents

Related product manuals