86
Transistor Output Units Section 4-4
Connector Pin Arrangement
Wiring Attach a FUJITSU connector to the Transistor Output Unit and connect it to
external devices.
Applicable Connectors
Three types of connectors can be attached to the cable, depending on the
assembly method. When creating your own cables, use one of the following
connectors.
Connector Cables
When a Transistor Output Unit (high-density connector) is to be connected to
an OMRON I/O Block or a Connector-Terminal Block Conversion Unit, use the
cables (sold separately) listed in the following table.
Note V terminals and G terminals are internally connected. When the I/O power is
being supplied, the power can be supplied to the output devices from the V
and G connectors. Current supplied in this way, however, must be less than
2 A. If, instead of using the V and G connectors, the power supply is wired to
the terminal block as shown in the following diagram, the current supplied
must be less than 4 A.
Pin number
Function
Pin number
Function
A20 A19 A18 A17 A16 A15 A14 A13 A12 A11 A10 A9 A8 A7 A6 A5 A4 A3 A2 A1
V G OUT
15
OUT
14
OUT
13
OUT
12
OUT
11
OUT
10
OUT
09
OUT
08
V
G
OUT
06
OUT
05
OUT
04
OUT
03
OUT
07
OUT
02
OUT
01
OUT
00
B20 B19 B18 B17 B16 B15 B14 B13 B12 B11 B10 B9 B8 B7 B6 B5 B4 B3 B2 B1
V G OUT
15
OUT
14
OUT
13
OUT
12
OUT
11
OUT
10
OUT
09
OUT
08
V G OUT
06
OUT
05
OUT
04
OUT
03
OUT
07
OUT
02
OUT
01
OUT
00
m+1 word
m word
Manufacturer Model number Remarks
FUJITSU FCN361J040-AU Soldered
FCN363J040-AU Crimp
FCN367J040-AU/F Pressure-welded
Manufacturer Model number Corresponding device
OMRON XW2Z-@@@B Connector-Terminal Block Conversion Unit
XW2B-40G4
XW2B-40G5
G79-O@C-@ I/O Block
G7TC-OC16, G7TC-OC08
G70D-SOC16, G70D-FOM16
G70A-ZOC16-3
M7F
Output Unit
I/O Block (example)
Load