222
Manual Control Level Section 5-8
Note When the Manual MV Limit Enable parameter is set to ON, the setting range
will be the MV lower limit to the MV upper limit.
■ Related Parameters
Standard or heating/cooling (initial setting level): Page 228
Monitor range Unit
Process value Temperature: According to indication range for
each sensor.
Analog: Scaling lower limit −5% FS to Scaling
upper limit +5% FS (Refer to page 335.)
EU
Set point SP lower limit to SP upper limit EU
Setting range Unit
MV (manual MV) Standard control −5.0 to 105.0
(See note.)
%
Heating/cooling control −105.0 to 105.0
(See note.)
Position-proportional control −5.0 to 105.0
(See note.)
See
See