222
Manual Control Level Section 5-8
Note When the Manual MV Limit Enable parameter is set to ON, the setting range
will be the MV lower limit to the MV upper limit.
â– Related Parameters
Standard or heating/cooling (initial setting level): Page 228
Monitor range Unit
Process value Temperature: According to indication range for
each sensor.
Analog: Scaling lower limit −5% FS to Scaling
upper limit +5% FS (Refer to page 335.)
EU
Set point SP lower limit to SP upper limit EU
Setting range Unit
MV (manual MV) Standard control −5.0 to 105.0
(See note.)
%
Heating/cooling control −105.0 to 105.0
(See note.)
Position-proportional control −5.0 to 105.0
(See note.)
See
See