This parameter enables or disables the LBA function and sets the detection
time interval.
• Set the time interval for detecting loop burnouts.
• To disable the LBA function, set 0.
■ Related Parameters
Alarm 1 type (initial setting level): Page 231
PID* LBA detection time (PID setting level): Page 219
LBA level: Page 259, LBA band: Page 260 (advanced function setting level)
• This parameter sets the LBA level.
• If the deviation between the SP and PV exceeds the LBA level, a loop
burnout is detected.
Note For ON/OFF control, the LBA Detection Time parameter (advanced
function setting level) must not be set to 0. For 2-PID control, the
LBA Detection Time parameter must not be set to 0 for any of PID
sets 1 to 8.
Note Set “None” as the unit for Controllers with Analog Inputs.
■ Related Parameters
Process value/Set point (operation level): Page 177
Alarm 1 type (initial setting level): Page 231
PID * LBA detection time (PID setting level): Page 219
LBA detection time, LBA band: Page 219 (advanced function setting level)
lba LBA Detection Time
Alarm 1 must be assigned.
The alarm type must be set to 12
(LBA).
ON/OFF control must be used.
Setting range Unit Default
0 to 9999 Second 0
Function
Setting
See
See
lbal LBA Level
Alarm 1 must be assigned.
The alarm type must be set to 12 (LBA).
The LBA detection time must not be 0.
(See note.)
Models Setting range Unit Default
Temperature input 0.1 to 3240.0 °C or °F8.0
Analog Input 0.01 to 99.99 %FS 10.00