279
Advanced Function Setting Level Section 5-10
• An ON/OFF count alarm occurs when the ON/OFF counter exceeds the
value set for this parameter.
• It is possible to assign ON/OFF count alarms to auxiliary outputs and to
have them displayed on the screen.
• This function is disabled when the set value is 0.
â–  Related Parameters
Control output 1 ON/OFF count monitor (advanced function setting level):
Page 278
• An ON/OFF count alarm occurs when the ON/OFF counter exceeds the
value set for this parameter.
• It is possible to assign ON/OFF count alarms to auxiliary outputs and to
have them displayed on the screen.
• This function is disabled when the set value is 0.
â–  Related Parameters
Control output 2 ON/OFF count monitor (advanced function setting level):
Page 278
ra1
Control Output 1 ON/OFF Count Alarm
Set Value
Control output 1 must be supported.
Relay, voltage outputs (for driving
SSR), or SSR output must be used.
Setting range Unit Default
0 to 9999 100 times 0
Function
Monitor
See
See
ra2
Control Output 2 ON/OFF Count Alarm
Set Value
Control output 2 must be supported.
Relay, voltage outputs (for driving
SSR), or SSR output must be used.
Setting range Unit Default
0 to 9999 100 times 0
Function
Monitor
See
See

Table of Contents

Other manuals for Omron E5AN-H

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Omron E5AN-H and is the answer not in the manual?

Omron E5AN-H Specifications

General IconGeneral
BrandOmron
ModelE5AN-H
CategoryTemperature Controller
LanguageEnglish

Related product manuals