(2) Unless the Program Pattern parameter is set to OFF, the bank number will be from 0 to the value
set for the Valid Program Bank parameter.
Adjustment Level
Parameters Characters Setting (monitor) value Display Default Unit Set value
Adjustment Level
Display
l.adj
AT Execute/Cancel at OFF: AT Cancel
AT-2: 100%AT Execute
AT-1: 40%AT Execute (See
note 3.)
off,
at-2,
at-1
OFF None
Communications
Writing
cmwt OFF, ON off, on OFF None
Infrared Communica-
tions Use
irdr OFF, ON off, on OFF None
SP Mode spmd LSP, RSP lsp, rsp LSP None
Heater Current 1
Value Monitor
ct1 0.0 to 55.0 A
Heater Burnout
Detection 1
hb1 0.0 to 50.0 0.0 A
Heater Overcurrent
Detection 1
oc1 0.0 to 50.0 50.0 A
Heater Current 2
Value Monitor
ct2 0.0 to 55.0 A
Heater Burnout
Detection 2
hb2 0.0 to 50.0 0.0 A
Heater Overcurrent
Detection 2
oc2 0.0 to 50.0 50.0 A
Leakage Current 1
Monitor
lcr1 0.0 to 55.0 A
HS Alarm 1 hs1 0.0 to 50.0 50.0 A
Leakage Current 2
Monitor
lcr2 0.0 to 55.0 A
HS Alarm 2 hs2 0.0 to 50.0 50.0 A
Heater Burnout
Detection 1
hb1 0.0 to 50.0 0.0 A
Heater Burnout
Detection 2
hb2 0.0 to 50.0 0.0 A
SP 0 sp-0 SP lower limit to SP upper
limit
0EU
SP 1 sp-1 SP lower limit to SP upper
limit
0EU
SP 2 sp-2 SP lower limit to SP upper
limit
0EU
SP 3 sp-3 SP lower limit to SP upper
limit
0EU
Temperature Input
Shift
ins −199.99 to 32400 0.00 °C or °F
Upper Limit Temper-
ature Input Shift
Value
insh −199.99 to 32400 0.00 °C or °F
Lower Limit Temper-
ature Input Shift
Value
insl −199.99 to 32400 0.00 °C or °F