327
Appendix
Remote SP Enable rspu OFF, ON off, on OFF None
Remote SP Upper
Limit
rsph SP lower limit to SP upper
limit
1300.0 EU
Remote SP Lower
Limit
rspl SP lower limit to SP upper
limit
−200.0 EU
SP Tracking sptr OFF, ON off, on OFF None
Remote SP Input
Error Output
rseo OFF, ON off, on OFF None
PID Set Automatic
Selection Data
pidi PV: Process Value
DV: Deviation
SP: Set point
pv
dv
sp
PV None
PID Set Automatic
Selection Hysteresis
pidh 0.10 to 99.99 0.50 %FS
PV Dead Band p-db 0 to 32400 0.0 EU
Manual MV Limit
Enable
manl OFF, ON off, on OFF None
Direct Setting of
Position Propor-
tional MV
pmvd OFF, ON off, on OFF None
PV Rate of Change
Calculation Period
pvrp 1 to 999 17 Sampling
period
Automatic Cooling
Coefficient Adjust-
ment
csca OFF, ON off, on OFF None
Heater Overcurrent
Use
ocu OFF, ON off, on ON None
Heater Overcurrent
Latch
ocl OFF, ON off, on OFF None
Heater Overcurrent
Hysteresis
och 0.1 to 50.0 0.1 A
PF Setting pf OFF: Not assigned
RUN: RUN
STOP: STOP
R-S: RUN/STOP
AT-2: 100% AT Execute
AT-1: 40% AT Execute
LAT: Alarm Latch Cancel
A-M: Auto/manual
PFDP: Monitor/setting item
BANK: Bank selection
off
run
stop
r-s
at-2
at-1
lat
a-m
pfdp
bank
A-M None
Monitor/Setting Item
1
pfd1 0: Disabled
1: PV/SP/Bank No.
2: PV/SP/MV
3: PV/SP/Soak time remain
4: Proportional band (P)
5: Integral time (I)
6: Derivative time (D)
7: Alarm value 1
8: Alarm value upper limit 1
9: Alarm value lower limit 1
10: Alarm value 2
11: Alarm value upper limit 2
12: Alarm value lower limit 2
13: Alarm value 3
14: Alarm value upper limit 3
15: Alarm value lower limit 3
16: Bank No.
1None
Monitor/Setting Item
2
pfd2 Same as for Monitor/Setting
Item 1.
0None
Parameters Characters Setting (monitor) value Display Default Unit Set value