328
Appendix
Monitor/Setting Item
3
pfd3 Same as for Monitor/Setting
Item 1.
0None
Monitor/Setting Item
4
pfd4 Same as for Monitor/Setting
Item 1.
0None
Monitor/Setting Item
5
pfd5 Same as for Monitor/Setting
Item 1.
0None
PV/SP Display
Screen Selection
spdp 0: PV/SP
1: PV/SP/Bank No.,
PV/SP/MV
2: PV/SP/MV, PV/SP/Bank
No.
3: PV/SP/Bank No.
4: PV/SP/MV
5: PV/SP/Bank No., PV/SP/
Soak Time Remain
6: PV/SP/MV, PV/SP/Soak
Time Remain
7: PV/SP/Soak Time Remain
4None
MV Display Selec-
tion
odsl O: MV (Heating)
C-O: MV (Cooling)
o
c-o
0None
PV Decimal Point
Display
pvdp OFF, ON off, on ON None
PV Status Display
Function
pvst OFF: OFF
MANU: Manual
STOP: Stop
ALM1: Alarm 1
ALM2: Alarm 2
ALM3: Alarm 3
ALM: Alarm 1 to 3 OR status
HA: Heater alarm
off
manu
stop
alm1
alm2
alm3
alm
ha
OFF None
SV Status Display
Function
svst OFF: OFF
MANU: Manual
STOP: Stop
ALM1: Alarm 1
ALM2: Alarm 2
ALM3: Alarm 3
ALM: Alarm 1 to 3 OR status
HA: Heater alarm
off
manu
stop
alm1
alm2
alm3
alm
ha
OFF None
Display Refresh
Period
d.ref OFF, 0.25, 0.5, 1.0 off
0.25
0.5
1.0
0.25 Second
Control Output 1 ON/
OFF Count Monitor
ra1m 0 to 9999 100 times
Control Output 2 ON/
OFF Count Monitor
ra2m 0 to 9999 100 times
Control Output 1 ON/
OFF Count Alarm
Set Value
ra1 0 to 9999 0 100 times
Control Output 2 ON/
OFF Count Alarm
Set Value
ra2 0 to 9999 0 100 times
ON/OFF Counter
Reset
rac 0 to 2 0 None
Move to Calibration
Level
cmov −1999 to 9,999 0 None
Parameters Characters Setting (monitor) value Display Default Unit Set value