2. Only the heater burnout alarm will be output from the alarm output 1 termi-
nals if alarm mode switch 1 is set to 0. Only the temperature alarm will be
output if the heater burnout alarm value is set to 0.0 A.
E5CJ Standard Model
Use the E54-CT1 with a hole
diameter of 5.8 mm or E54-CT3 with a hole
diameter of 12 mm (both sold separately).
(Heater burnout alarm
and temperature alarm)
1
2
3
4
5
14
13
12
11
6
7
8
9
10
9
10
9
10
+
A
B
B
+
+
(ALM1)
12 VDC
CT
Control output (OUT)
Event input 1 (EV1) Exter-
nally selects the set point.
See note 2.
Alarm
output 1
1 A (resistive load)
at 250 VAC
Alarm output 2
Voltage Output Unit
(20 mA max.)
Current Output Unit
4 to 20 mA DC
(with a load of 600 max.)
Relay Output Unit
3 A (resistive load)
at 250 VAC
See note 1.
open
short-circuit
+
100 to 240 VAC, 50 or 60 Hz, 12 VA
or
24 VAC, 50 or 60 HZ, 10 VA
24 VDC 6 W
Note 1. The event input terminals and voltage output and current output terminals
are not insulated.
2. Only the heater burnout alarm will be output from the alarm output 1 termi-
nals if alarm mode switch 1 is set to 0. Only the temperature alarm will be
output if the heater burnout alarm value is set to 0.0 A.
3. A simple model with no alarm does not incorporate any event input or alarm
output. A simple model with an alarm function does not incorporate any
event input.
Terminal Arrangement
Section 5-3