4.3 Setting Scaling Upper and Lower Limits (analog input)
4-9
In this example, let's set the scaling upperĆ and lowerĆlimits so that inputs
0 to 50 mV become 10.0% to 95.0%.
(1) Press the key for at least three seconds to move from the operaĆ
tion level" to the initial setting level".
(2) Select scaling upper limit" by pressing .
(3) Use the keys to set the parameter to 950".
(4) Select scaling lower limit" by pressing .
(5) Use the keys to set the parameter to 100".
(6) Select the decimal point position by pressing .
(7) Use the keys to set the parameter to 1".
(8) To return to the operation level" press the key for at least one
second.
Operation Procedure
Input type
Initial settinglevel
Scaling upperlimit
Scaling lowerlimit
Decimalpoint