EasyManua.ls Logo

Omron SYSMAC CS/CJ Series

Omron SYSMAC CS/CJ Series
383 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
242
Cycle Time/High-speed Processing Section 6-1
6-1-9 Maximum Data Link I/O Response Time
Normal Processing The following diagram illustrates the data flow that will produce the maximum
data link I/O response time when DLNK(226) is not used.
There are three points shown in the diagram above where processing is
delayed, increasing the data link I/O response time.
1,2,3... 1. The input arrives in the PLC (CPU Unit #1) just after I/O refreshing, caus-
ing a delay of one cycle before the input is read into the PLC. CPU Bus
Units are refreshed after program execution, causing a total delay of two
cycle times.
2. Data exchange occurs just after the PLC passes the token that makes it
the polling node, causing a delay of up to one communications cycle time
before the data is transferred in data link processing. There will also be a
delay of up to one communications cycle time after receiving the token,
causing a total delay of up to two communications cycle times.
3. The data transferred in data link processing arrives at the PLC (CPU Unit
#2) after data exchange, so the data will not be read into the PLC until the
next data exchange, causing a delay of up to one cycle. CPU Bus Units
are refreshed after program execution, causing a total delay of two cycle
times.
The equation for maximum data link I/O response time is as follows:
×
×
×
Input Unit
Input
Input ON delay
(1) Delay of two cycle times
Basic I/O Units
refreshed.
CPU Bus Units refreshed
(including data links)
One cycle time
Data transfer to
Controller Link Unit
Processing in
CPU Unit #1
(2) Delay of two communications cycle times
One com-
munica-
tions cycle
Data link transmissions
(3) Delay of two cycle times
Data received from Controller Link Unit
One cycle time
Output Unit
Output ON delay
Processing in
CPU Unit #2
Maximum data link I/O response time
Program
execution
Program
execution
Input ON delay 1.5 ms
Cycle time of PLC at CPU Unit #1 × 225 ms × 2
Communications cycle time × 210 ms × 2
Cycle time of PLC at CPU Unit #2 × 220 ms × 2

Table of Contents

Related product manuals