EasyManua.ls Logo

Omron SYSMAC CS/CJ Series

Omron SYSMAC CS/CJ Series
383 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
268
Serial Communications Section 6-3
6-3-2 No-protocol Communications
The following table lists the no-protocol communication functions available in
CS/CJ PLCs.
Note A transmission delay or “no-protocol mode delay” can be specified in the PLC
Setup (address 162). This setting causes a delay of up to 30 seconds
between execution of TXD(236) and the transmission of data from the speci-
fied port.
Procedure
Message Frame Formats
Data can be placed between a start code and end code for transmission by
TXD(236) and frames with that same format can be received by RXD(235).
When transmitting with TXD(236), just the data from I/O memory is transmit-
ted, and when receiving with RXD(235), just the data itself is stored in I/O
Transfer direction Method Max. amount
of data
Frame format Other
functions
Start code End code
Data transmission
(PLC External device)
Execution of TXD(236)
in the program*
256 bytes Yes: 00 to FF
No: None
Yes:
00 to FF or CR+LF
No: None
Send delay
time (delay
between TXD
execution and
sending data
from specified
port): 0 to
99,990 ms
(unit: 10 ms)
Data reception
(External device PLC)
Execution of RXD(235)
in the program
256 bytes ---
Set the PLC Setup from a Pro-
gramming Device.
(Settings such as the communica-
tions mode and parameters.)
Programming Console
Set addresses 160 to 163. In particular, set
the communications mode to no-protocol
mode, set the start code, end code, amount of
data, and no-protocol mode delay.
(Refer to CX-Programmer User Manual for
CX-Programmer procedures.)
Power OFF
Connect the CPU Unit and external
device through the RS-232C port
Set the DIP switch on the front of
the CPU Unit.
Turn pin 5 OFF.
Power ON
PLC External device
External device PLC
Execute TXD(236).
Execute RXD(235).

Table of Contents

Related product manuals