9 Specifications
241
Fourth Functions (Constants n120 to n179)
No. Register
No. for
Trans-
mission
Name Setting Range Setting Unit Factory
Setting
Change
during
Opera-
tion
User
Set-
ting
Ref.
Page
120 0178 Frequency Reference 9 0.00 to 400.0
Hz
0.01 Hz
(less than
100 Hz)/0.1
Hz (100 Hz
or more)
0.00 Hz Yes 74
121 0179 Frequency Reference 10 0.00 to 400.0
Hz
0.01 Hz
(less than
100 Hz)/0.1
Hz (100 Hz
or more)
0.00 Hz Yes 74
122 017A Frequency Reference 11 0.00 to 400.0
Hz
0.01 Hz
(less than
100 Hz)/0.1
Hz (100 Hz
or more)
0.00 Hz Yes 74
123 017B Frequency Reference 12 0.00 to 400.0
Hz
0.01 Hz
(less than
100 Hz)/0.1
Hz (100 Hz
or more)
0.00 Hz Yes 74
124 017C Frequency Reference 13 0.00 to 400.0
Hz
0.01 Hz
(less than
100 Hz)/0.1
Hz (100 Hz
or more)
0.00 Hz Yes 74
125 017D Frequency Reference 14 0.00 to 400.0
Hz
0.01 Hz
(less than
100 Hz)/0.1
Hz (100 Hz
or more)
0.00 Hz Yes 74
126 017E Frequency Reference 15 0.00 to 400.0
Hz
0.01 Hz
(less than
100 Hz)/0.1
Hz (100 Hz
or more)
0.00 Hz Yes 74
127 017F Frequency Reference 16 0.00 to 400.0
Hz
0.01 Hz
(less than
100 Hz)/0.1
Hz (100 Hz
or more)
0.00 Hz Yes 74
128 0180 PID Control Selection 0 to 8 - 0 No 159
129 0181 PID Feedback Gain 0.00 to 10.00
Hz
0.01 1.00 Yes 162
130 0182 Proportional Gain (P) 0.0 to 25.0 0.1 1.0 Yes 161
131 0183 Integral Time (I) 0.0 to 360.0 s 0.1 s 1.0 s Yes 161
132 0184 Derivative Time (D) 0.00 to 2.50 s 0.01 s 0.00 Yes 161