9 Specifications
243
153 0199 MEMOBUS Slave Address 0 to 32 - 0 No 144
154 019A MEMOBUS BPS Selection 0 to 3 - 2 No 144
155 019B MEMOBUS Parity Selection 0 to 2 - 0 No 144
156 019C Transmission Waiting Time 10 to 65 ms 1 ms 10 ms No 144
157 019D RTS Control 0, 1 - 0 No 144
158 019E Motor 2 Maximum Voltage 0.1 to 255.0 V
(Note 2)
0.1 V 200.0 V
(Note 2)
No 99
159 019F Motor 2 Mid. Output
Frequency Voltage
0.1 to 255.0 V
(Note 2)
0.1 V 12.0 V
(Note 2)
(Note 3)
No 99
160 01A0 Motor 2 Minimum Output
Frequency Voltage
0.1 to 50.0 V
(Note 2)
0.1 V 12.0 V
(Note 2)
(Note 3)
No 99
161 01A1 Motor 2 Rated Current 0% to 150% of
Inverter rated
current
0.1 A (Note 3) No 99
162 0192 Motor 2 Rated Slip 0.0 to 20.0 Hz 0.1 Hz (Note 3) No 99
163 01A3 PID Output Gain 0.0 to 25.0 0.1 1.0 No 162
164 01A4 PID Feedback Value Selection 0 to 5 - 0 No 160
165 01A5 Externally Mounting Type
Braking Resistor Overheat
Protection Selection
(Note 7)
0, 1 - 0 No -
166 01A6 Input Open-phase Detection
Level
0% to 100% 1% 0% No 184
167 01A7 Input Open-phase Detection
Time
0 to 255 s 1 s 0 s No 184
168 01A8 Output Open-phase Detection
Level
0% to 100% 1% 0% No 184
169 01A9 Output Open-phase Detection
Time
0.0 to 2.0 s 0.1 s 0.0 s No 184
170 01AA Enter Command Operation
Selection (MEMOBUS
communications)
0, 1 - 0 No 155
171 01AB Frequency Reference Bias
Upper Limit (Up/Down Com-
mand 2)
0.0% to
100.0%
(n011 = 100%)
0.1% 0.0% Yes 115
172 01AC Frequency Reference Bias
Lower Limit (Up/Down Com-
mand 2)
-99.9% to
0.0%
(n011 = 100%)
0.1% 0.0% Yes 115
No. Register
No. for
Trans-
mission
Name Setting Range Setting Unit Factory
Setting
Change
during
Opera-
tion
User
Set-
ting
Ref.
Page