6.7 MULTI STATE VALUE
Property Default Value Read-only or
Writable
Comment
Object Identier Multi-state-value, 1 Read-only
Object Name Meter Status Read-only
Object Type Multi-state-value Read-only
Present Value 1 Writable
Description Multi-state-value, # Name Read-only
Status Flags (F,F,F,F) Read-only
Event State Normal Read-only
Reliability No-fault-detected Read-only
Out-of-Service FALSE Writable
Number of States 11 Read-only
State Text Normal, Low Supply Temperature,
High Supply Temperature, Low Return
Temperature, Delta T< Minimum,
High Energy Rate, Low Signal Quality,
Comm Error, Low Supply Voltage,
System Fault
Read-only
Relinquish Default 0 Read-only
Multi-state Object
Object Identier Description Notes
Multi-state Value 1 Reports the operating status of the meter
1 = Normal
2 = Low Supply Temperature
3 = High Supply Temperature
4 = Low Return Temperature
5 = High Return Temperature
6 = Delta T < Minimum
7 = High Energy Rate
8 = Low Signal Quality
9 = Comm error
10 = Low Supply Voltage
11= System Fault
Numeric values indicate meter
status.