F-4600 With LCD Flow Meter Manual 06/18 - 2020-3 / 35874 Page 23
6.3 DEVICE OBJECT
Property Default Value Read-only or
Writable
Comment
Object Identier 57017 Writable 0-4,194,303
Object Name F-4600-BAC Read-only
Object Type Device Read-only
System Status Operational Read-only
Vendor Name ONICON Incorporated Read-only
Model Name F-4600-BAC Read-only
Firmware Rev. 000.000.000 Read-only
Location Customer Location Writable 32 char. max
Description Customer Description Writable 32 char. max
Protocol Version 1 Read-only
Protocol Revision 10 Read-only
Services Supported Read property, Read property multiple,
Write property, Write property
multiple, Read range, Who-has, I have,
Who-is, I-am, Device communications
control, Time synchronization, UTC
time synchronization
Read-only
Object Types Supported Analog input, Analog value, Binary
input, Device, Multi-state value, Trend
log multiple
Read-only
Object List (Device, 57017), (analog input, 1 – 10),
(analog value, 1 – 22), (binary value,
1 – 10), (trend log multiple, 1), (multi
state value, 1)
Read-only
Max ADPU Length 480 Read-only
Local Time Device current time Read-only
Local Date Device current date Read-only
UTC Offset -300 Writable
Daylight Savings Status False Writable
APDU Timeout 6000 Read-only
# of APDU Retries 3 Writable
Max Master 127 Read-only
Device Address Binding Read-only
Database Revision 1 Read-only