8.4 ANALOG OUTPUT
When congured with an auxiliary analog output, your F-4600 with optional LCD display will be
equipped with the ability to send a single analog signal to a remote device or building automation
system. The analog output can be programmed in the commissioning menu for 4-20 mA, 0-5 V, or
0-10 V output types. The factory default is 4-20 mA.
The following meter values are available to be mapped to the analog output:
Volume Rate
Fluid Temperature
The analog output minimum and maximum are also congured in the commissioning menu. The
minimum value set in programming will be what the 4 mA or 0 V is equivalent to. The maximum
value set in programming will be what the 20 mA/5 V/10 V is equivalent to.
Example: A 4-20 mA analog output congured as uid temperature with a minimum of 30
and maximum of 80 will have an output signal of
4-20 mA = 30 - 80° F.
The units of measurement for the analog output will match the LCD description on the F-4600.
When cycling through the F-4600 run pages, if the F-4600 is equipped with an analog output, the
page which corresponds to the analog output will have the output signal type and scaling shown
on it.