FT
-
3500 ELECTROMAGNETIC FLOW METER
ONICON Incorporated 727.447.6140 Page 33 onicon.com
Access this screen through Main Menu --> User
Cong --> Network
Access this screen through Main Menu --> User
Cong --> Network
User Conguration
Access this screen through Main Menu --> User
Cong
User Cong: This function enables users to examine and
congure the meter’s network, inputs and outputs, pipe setup,
operating mode, and eld characterization.
Network Type Settings
The communications menu oers options to choose the
meter’s network output. To conrm selections, use the “Apply”
button. Available settings include None, BACnet/MSTP, BACnet
IP, MODBUS RTU, and MODBUS TCP/IP.
For BACnet/MSTP and MODBUS RTU:
Max Master (BACnet Only): Max number of devices in the
trunk range 0-127. A repeater is needed if the trunk has more
than 32 devices.
Address: This is the Device ID which must be unique for the
device across the whole BACnet network. Range: 0-127
Baud: Baud Rate, or Bits Per Second. Denes the speed of
communication on the BUS. Must be the same for all devices
on the BUS. Options: 9600, 19200, 38400, 57600, 76800.
Instances (BACnet Only): Provide a unique number for the
meter in the trunk.
Stop Bit (MODBUS Only): default to 1
Parity (MODBUS Only): Selectable as None, Even or Odd.