3500 ELECTROMAGNETIC FLOW METER
ONICON Incorporated 727.447.6140 Page 33 onicon.com
Access this screen through Main Menu --> User
Cong --> Network
Access this screen through Main Menu --> User
Cong --> Network
User Conguration
Access this screen through Main Menu --> User
Cong
User Cong: This function enables users to examine and
congure the meter’s network, inputs and outputs, pipe setup,
operating mode, and eld characterization.
Network Type Settings
The communications menu oers options to choose the
meter’s network output. To conrm selections, use the “Apply”
button. Available settings include None, BACnet/MSTP, BACnet
IP, MODBUS RTU, and MODBUS TCP/IP.
For BACnet/MSTP and MODBUS RTU:
Max Master (BACnet Only): Max number of devices in the
trunk range 0-127. A repeater is needed if the trunk has more
than 32 devices.
Address: This is the Device ID which must be unique for the
device across the whole BACnet network. Range: 0-127
Baud: Baud Rate, or Bits Per Second. Denes the speed of
communication on the BUS. Must be the same for all devices
on the BUS. Options: 9600, 19200, 38400, 57600, 76800.
Instances (BACnet Only): Provide a unique number for the
meter in the trunk.
Stop Bit (MODBUS Only): default to 1
Parity (MODBUS Only): Selectable as None, Even or Odd.