3500 ELECTROMAGNETIC FLOW METER
ONICON Incorporated 727.447.6140 Page 34 onicon.com
Access this screen through Main Menu --> User
Cong --> Network
Access this screen through Main Menu --> User
Cong --> Network
Access this screen through Main Menu --> User
Cong --> Network
For BACnet IP and MODBUS TCP/IP:
Network Address: numerical label assigned to the FT-3500.
Network Mask: Divide the Network address into the subnet
and specify the network available.
Gateway: Access point numerical conguration for data to
travel between dierent networks
Foreign IP: If there is a BACnet controller on a dierent
network (via a router) that should be used with the meter, its
address is specied in this eld.
Foreign Port: If there is a BACnet controller on a dierent
network (via a router) that should be used with the meter, its
network port is specied in this eld.
TCP Port (MODBUS Only): Specic port assigned to MODBUS
TCP/IP network.
UDP Port (BACnet Only): Specic port assigned to BACnet
UDP/IP network.
DHCP: Check to activate Dynamic IP Address. Uncheck box
means the meter can be congured for Static IP Address.