3500 ELECTROMAGNETIC FLOW METER
ONICON Incorporated 727.447.6140 Page 35 onicon.com
Access this screen through Main Menu --> User
Cong --> Input/Output
Inputs & Outputs
Through the Inputs & Outputs screen the user can make
changes to analog output, digital input/output, or frequency
output.
Access this screen through Main Menu --> User
Cong --> Input/Output --> Analog Output
Analog Outputs: FT-3500 has two analog outputs (Terminal
TB3-1 and TB3-2). Terminal TB3-1 is Output 1 and terminal
TB3-2 is Output 2.
Output Options: Energy, Energy Heating, Energy Cooling,
Supply Temp, Return Temp, Delta Temp.
Analog Out Max: Numeric value set via the keypad. If chang-
ing this setting, ensure that the new analog out max is greater
than the max ow your system can do.
Analog Out Range: Options include 4-20mA and 2-10V,
4-20mA and 1-5V, 4-20mA and 0-10V, 4-20mA and 0-5V. If
4-20mA and 2-10V is selected, the meter will report 2mA or
1V when it is in alarm. If 1-5V is selected, the meter will report
0.5V when it is in alarm. If 0-10V is selected the meter will
show 0V when the meter is in an alarm or zero ow.
Units: This option will display the units selected under Main
Menu->Preference->Units.