3500 ELECTROMAGNETIC FLOW METER
ONICON Incorporated 727.447.6140 Page 36 onicon.com
Access this screen through Main Menu --> User
Cong --> Input/Output --> Digital I/O
Access this screen through Main Menu --> User
Cong --> Input/Output --> Digital I/O
Digital I/O: Start by selecting which output the user intends to
edit: IO 1, IO 2, or IO 3, Set to Input or Output.
IO 1, IO2 or IO3 / Input: congurable as None or Contact
Count. This can be used for any close contact totalization
meter to be brought to the network.
Note: Set the Jumper J1-J2, J3-J4, J5-J6 on Input
position if this feature is needed
IO 1, IO2 or IO3 / Output: Close contact output for the
FT-3500. Output Options can be congured to None,
Volume, Volume Forward, Volume Reverse, BTU Total Pulse
Outputs, Alarm, Mode Status, or Warning
For Volume, Volume Forward, Volume Reverser:
Pulse Factor: 1, 10, 100, 1K, 10K, 100K, or 1M is the
quantity of the selected units at which the meter will
close the output.
Pulse Duration: Duration of the close contact and
the total cycle. Congurable as 50msOn1SecTotal,
100msOn1SecTotal, 500msOn2SecTotal,
1000msOn3SecTotal.
Note: Improper conguration on the unit might
result in a pulse over-run alarm.
Units: This option will display the units selected under
Main Menu->Preference->Units.
For Alarm:
If this option is selected, the meter will close the contact if
it is ever in an alarm state.
For Warning:
If this option is selected, the meter will close the contact if
it is ever in warning state.
Note: Warning does not aect the operation of the
meter