3500 ELECTROMAGNETIC FLOW METER
ONICON Incorporated 727.447.6140 Page 42 onicon.com
Signal Connections:
The signal connections screen will give the user the connection
status of the meter’s electromagnetic sensors/coil, temperature
sensors/ RTDs (if using as an energy meter), and transmitter
output status.
Note that ow is required for an accurate sensor
connectivity status.
Network Diagnostics:
The user can verify their communication status via the Network
Diagnostics screen.
Comm Status:
Down: No trac has been seen in 60 seconds
Up, Active: Trac has been seen in the last 60 seconds,
and the meter is talking to the network.
Up, Inactive: Trac has been seen in the last 60
seconds, and the meter is not talking to the network.
User Test:
The user test mode can be enabled to allow the user to
simulate ow. When User Test is enabled, the user will see a
red user test symbol located in the bottom right corner next to
the home icon.
While in User Test mode, the user can simulate ow by:
Percentage of full scale.
Feet per minute.
Gallon per minute.
To exit out of the User Test mode, set the rst drop-down box
to “Disabled”.