EasyManuals Logo

Overkill Solar BMS Series User Manual

Overkill Solar BMS Series
68 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #21 background imageLoading...
Page #21 background image
3.2.6 80%, 60%, 40%, 20% Capacity Voltage Levels
This should be set to the cell’s voltage at each of the four indicated state of charge levels. This information
typically comes from the battery cell’s datasheet, which may may involve interpreting the discharge curve
graph. However, the recommended values in Appendix A may be used.
3.3 Balance Parameters
3.3.1 Start Voltage
The BMS will not begin its balancing routine until the cell voltage(s) are above this voltage. Typically this
parameter should be set towards the top of the battery’s voltage curve.
3.3.2 Delta to balance
The BMS will not balance unless the delta exceeds this level. Setting this value too coarse will result in
possible cell damage; setting this value too fine will result in the BMS dissipating considerable heat as it
attempts to equalize the cell voltages. Recall that the passive balancing circuit works by routing the excess
voltage into resistors within the BMS, which converts into heat. This value must be a compromise between
those two extremes. Please see the recommended values in Appendix A.
3.3.3 Balancer Enabled
The BMS will only perform its balancing routine if this option is enabled.
There are very few reasons why this would ever be turned off. We recommend to keep it enabled.
3.3.4 Balance only when Charging
When enabled, the balancing routine will only be performed when charging.
When disabled, the BMS will enter Static Balance mode, where it will balance when both charging and
discharging.
NOTE: Charging while balancing is usually more effective, because the cell delta is greatest at the top of the
charge. We recommend to keep this setting enabled.
3.4 Other Parameters / Features
3.4.1 Switch
When enabled, the discharge FET will be disabled when the optional external switch contact is open. This
external switch, if used, must be wired to the 2-pin JST-XH connector on the BMS (see Appendix D1.3).
When disabled, the external switch will not be monitored or read.
3.4.2 Load Detect
When enabled, you will need to disconnect the load after a short-circuit before the battery pack can be used
again.

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Overkill Solar BMS Series and is the answer not in the manual?

Overkill Solar BMS Series Specifications

General IconGeneral
BrandOverkill Solar
ModelBMS Series
CategoryControl Unit
LanguageEnglish

Related product manuals