EasyManuals Logo

Overkill Solar BMS Series User Manual

Overkill Solar BMS Series
68 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #45 background imageLoading...
Page #45 background image
Click the “Idle Calibration” button. The app should display a message that the calibration command was sent
to the BMS.
B.2.2 Charge Current Calibration
This test cannot be done when the batteries are fully charged. It is recommended to perform this step when
the batteries are no more than 80% capacity.
Connect your MPPT controller or shore charger. If you are using MPPT / solar, ensure that it is a sunny day
with all panels exposed to full sunlight. If you have multiple chargers, choose whichever is capable of charging
the system the fastest. You may also use several chargers simultaneously; just do not exceed the maximum
charge current of the BMS or the batteries. At this point, turn on the charger(s), and verify that they are
running in the correct mode (e.g. bulk mode). Refer to your charger’s user manual if necessary.
Clamp the current meter around the positive battery cable. Turn the meter on and to the highest DC current
measurement range. if your meter has multiple current ranges, always start on the highest range, and only
move down to the lower range(s) if the measured current is lower than the next lower range. For example, if
your meter has two ranges, 400A and 40A, then start on 400A, and only move down to 40 if the current
measures less than 40. This will ensure that you do not damage your meter.

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Overkill Solar BMS Series and is the answer not in the manual?

Overkill Solar BMS Series Specifications

General IconGeneral
BrandOverkill Solar
ModelBMS Series
CategoryControl Unit
LanguageEnglish

Related product manuals