Differential cut-out
We advise you to protect the installation with a differential cut-out of no more than 30 mA. This cut-out has
to be choosen in function of the installed electrical power.
It is advisable to foresee a main switch for the electrical supply of the milk cooling tank. In case the main
electrical cable is equipped with a plug, it is not necessary to install an extra circuit breaker.
Check the local regulations.
The main switch must be lockable in the OFF position
Earth
The installation must have a good earth, earth resistance ≤ 5 Ohm, earth wire min. 6mm². Also to be checked
with the local regulations.
Bonding
The bonding has to be installed
by means of a yellow/green wire
with 6 mm², near the
connection clamp ,
foreseen on the tank, the cooling
unit and the main earth
connection of the building and
must be continuous.
Do not connect the
bonding to the earth terminal
strip in the electrical panel!
Power
Hereafter, the power (P) and the intensity (I) of the different cooling tanks.
REM/DX, RS/DX