2000  - FIRE ALARM SOLUTIONS TECHNICAL DESCRIPTION
17
4.3.  PROGRAMMABLE VOLTAGE OUTPUTS (S1)
The 24 V DC output S1 is normally supervised. The output is in EBLWin default set as supervised, but via EBLWin it is possible to 
set the output to be not supervised or supervised with EOL. LPS output.
Voltage
 Active:
             Supervised:
22.0 – 25.0 V DC (nom. 23.5 V DC)
~ - 5 V DC
Current
  Active:
             Supervised:
≤ 250m A
~ - 1 mA
Line resistance RL:
≤ 32 Ohm depending on current outtake and allowed 
voltage of the connected device.
Outputs S1 is protected by a resettable PTC Fuse.
S1 is connected to terminal block J6: 1-2. 
      
See also chapter Programmable outputs in EBLOne Planning instructions.
For EN54-13 compliance, End-of-line device type 4472 shall be mounted after the last unit on the line.
4.4.  PROGRAMMABLE INPUTS (I1-I2)
In the CIE are two programmable inputs (I1-I2) available. Each input can either be used as a general input or as interface to an 
alarm transmission or fault warning routing equipment. 
JP1* JP2*
Open Shunted Open Shunted
I1 used as a general input. I1 used as interface to an alarm transmis-
sion routing equipment (ATX). 
I2 used as a general input I2 used as interface to a fault warning 
routing equipment (FTX). 
* Note, JP1 and JP2 consist of three jumpers each, all three jumpers shall be either open or shunted. JP1 and JP2 are default set to open.
4.4.1.  USED AS GENERAL INPUT
Input used as general input. All three jumpers on JP1 and JP2 shall be open.
NOT SUPERVISED
Normally open (R > 100k Ohm) 
Normally closed (R < 10k Ohm)
Activation time: > 1 sec.
Voltage output S1