2000 - FIRE ALARM SOLUTIONS TECHNICAL DESCRIPTION
7
3. GENERAL DESCRIPTION
The control and indicating equipment is a unit, to which the alarm points are connected via the COM loop. It indicates re alarm,
fault condition, and so on. EBLOne can have up to 253 addresses, and up to 253 alarm points.
The unit is intended for indoor use and in dry premises.
EBLOne conforms to the European standard EN54, part 2 and 4.
3.1. OPTIONS
EN 54-2 options with requirements Clause in EN 54-2:1997/A1:2006
Output to re alarm devices 7.8
Output to re alarm routing equipment 7.9.1
Delays to outputs 7.11.1 b) + c) + d) + e) + f)
Dependencies on more than one alarm signal (Type B) 7.12.2
Alarm counter 7.13
Fault signals from points 8.3
Output to fault warning routing equipment 8.9
Test condition 10
Standardized input/output interface 11