2000 - FIRE ALARM SOLUTIONS TECHNICAL DESCRIPTION
31
9. TECHNICAL DATA 2000
All current consumptions are valid by nominal voltage and by 25 °C.
Voltage:
Primary
System
230V AC (195 - 253) 1.1 A, 50 Hz
24V DC
Rated output voltage 22.0 – 25.0V (Max ripple 300 mVp-p)
Current:
Quiescent / Active
Max 1500 mA
Depending on connected external equipment.
Number of addresses Maximum 253
Number of alarm points Maximum 253
Short circuit isolator Yes, for one loop
Internal battery Not included
Material PBS / ABS
Ambient temperature:
Operating
Storage
-5 to +40 °C (indoor use only)
-30 to +60 °C
Ambient humidity Maximum 95 % RH (Non condensing)
Altitude < 2000 m above sea level
Ingress protection rating IP30
Acceptable pollution degree Degree1 and 2: None or dry, non-conductive pollution
Size:
H x W x D
422 x 310 x 122 mm
Weight: 4 kg (no internal batteries)
Colour RAL 9003