53
6 Using the System
6.8 Auxiliary Settings
6.8.1 Registering zone names
You can assign names to zones.
Zones are unrelated to distribution, so you can mix GHP, PAC, and HOT units, and make settings
that extend across link systems.
Start/stop, monitoring, timer operation and so on can be done all at once for all units in a zone.
Procedure
Select 6.Auxiliary settings in the main menu and 1.Zone name in the sub menu.
1
1.Status/Control
2.Total data/Cut-off
3.Distrib. ratio/Usage
4.Maintenance/Test Run
5.Initial settings
6.Auxiliary settings
1.Zone name
2.ZoneNo./Mng.target
3.Program timer
4.Ten.Ho/TimerSp.Day
5.Prohibit R/C
6.Distribution time zone
7.Special distrib. day
8.I/D unit settings
10.WEB settings
11.User settings
9.Other settings
1
Select a name to register or modify. A software keyboard appears.
2
Enter the name with the keyboard.
Names can be up to 20 characters long.
* See “7 Entering Text and Numbers” for details about entering text in keyboard windows.
* Zones name can be registered in the range 1 to 128.
Main
Sub
1
1
6
6