84
10 Calculating air conditioner distribution
Calculate electricity/gas usage index of entire distribution group
Let “TOTALe” be the electricity usage index of entire distribution group,
and let “TOTALg” be the gas usage index of entire distribution group.
Let “m” be the number of indoor units in the distribution group.
TOTALe = TE1 + TE2 + ··· + TEm
TOTALg = TG1 + TG2 + ··· + TGm
Calculate electricity/gas usage distribution ratio of indoor units
Let “REi” be the electricity usage distribution ratio,
and let “RGi” be the gas usage distribution ratio.
REi (%) = TEi / TOTALe × 100
RGi (%) = TGi / TOTALg × 100
Calculate electricity/gas usage distribution ratio of tenant j
Let “NEj” be the electricity usage distribution ratio of tenant j,
and let “NGj” be the gas usage distribution ratio of tenant j.
Let “n” be the number of indoor units of tenant j.
NEj (%) = RE1 + RE2 + ··· + REn
NGj (%) = RG1 + RG2 + ··· + RGn
Distribution ratios are rounded at the third decimal place and shown to the second decimal place.
* The following table shows which of the formulas
1
to
3
on the previous page are used by the two
distribution modes.
T/S ON+OFF time
distribution mode
T/S ON time
distribution mode
GHP
Electricity
12
Gas
22
PAC
Electricity
32
Gas
--
HOT
Electricity
32
Gas
2
2
See “About distribution ratios in 12 Supplementary Information-2”.